Wired flush mount temperature sensor for Lutron HVAC Controller.

Features:

  • 5 year battery life
  • Main repeaters/RF links
  • Accurate to +/- 1 °F
  • Multiple sensor averaging possible
  • Flexible mounting options require no wiring

 

Specifications:


Power HVAC Controller: 24 V~ IEC PELV/NECR Class 2 Wireless Temperature Sensor: 3 V- (one CR2450 battery included)
Typical Power Consumption HVAC Controller: 3 W; Test conditions: two LEDs on
Regulatory Approvals HVAC Controller: UL, cUL, FCC, IC, COFETEL WirelessTemperature Sensor: UL, cUL, FCC, IC, COFETEL
Environment HVAC Controller: Ambient operating temperature: 32 °F to 160 °F (0 °C to 71 °C), 0% to 90% humidity, non-condensing. Indoor use only. Wireless Temperature Sensor, Wired Return Air Duct Sensor, and Wired Flush Mount Sensor: Ambient operating temperature: 32 °F to 104 °F (0 °C to 40 °C), 0% to 90% humidity, non-condensing. Indoor use only.
Communications LutronR Comfort Controls communicate with the system through Radio Frequency (RF) and must be located within 30 ft (9 m) of a repeater. System devices operate on frequencies between 431.0 MHz and 437.0 MHz.
ESD Protection Tested to withstand electrostatic discharge without damage or memory loss, in accordance with IEC 61000-4-2.
Surge Protection Tested to withstand surge voltages without damage or loss of operation, in accordance with IEEE C62.41-1991 Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits.
Power Failure Power failure memory: should power be interrupted, the Comfort Controls will retain their programming when power is restored.
Mounting HVAC Controller: Mount on flat surface using supplied screws. Wireless Temperature Sensor: Adhesive strip provided for temporary mounting and testing. Wall anchor and screw provided for permanent mounting. Wired Return Air Duct Sensor: Mount in return air duct using supplied screws. Wired Flush Mount Sensor: Surface mount in area to be controlled.
Wiring HVAC Controller: IEC PELV/NECR Class 2, 22 AWG (0.5 mm2 ) to 18 AWG (0.75 mm2 ) solid wiring. Requires transformer common connection. Wired Return Air Duct Sensor: IEC PELV/NECR Class 2, 22 AWG (0.5 mm2 ) to 18 AWG (0.75 mm2 ) twisted, shielded pair wiring. Maximum wire length is 100 ft (30.5 m). Wired Flush Mount Sensor: IEC PELV/NECR Class 2, 22 AWG (0.5 mm2 ) twisted, shielded pair wiring. Maximum wire length is 100 ft (30.5 m).
Warranty

http://www.lutron.com/TechnicalDocumentLibrary/Warranty.pdf - Warranty only valid if installed by climate control specialist.

 



Prop 65WARNING: This product contains chemicals including Styrene which is known to the state of California to cause cancer, and Bisphenol A (BPA), which is known to the state of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.



In certain instances promotional prices will be offered listed above as a “Price with Rebate”, and are typically dated. In these cases Instant Rebate (IR) pricing is good sometimes only for the day only or only for the week. In order to be eligible for IR pricing – the order must be paid for AND picked up/shipped out. If you are placing an online order outside of business hours within your respective time zone, please add a note to your order for the team to confirm the pricing, or contact the branch the following business day to ensure that the item pricing carries over into the subsequent period. If an alternate branch location is still open in another time zone, please reach out to that group.